Add£ºNo. 508 Ganglong Road, Economic Development Zone, Yangzhong City, Jiangsu Province (212213 )
    Tel: 0511-88219009
    E-mail:sales@jsyineng.com

HXGN15-12 air-insulated ring main unit

Publisher£ºYineng group Release time£º2018/12/29 10:16:26 Click on the£º1343 Shut down






  • 1.Ambient air temperature: -15¡æ~+40¡æ. Daily average temperature:¡Ü35¡æ. 
    2.Altitude: ¡Ü1000m.

    3.Relative humidity : Daily average¡Ü95% ,daily averange of vapour pressure¡Ü2.2kpa Monthly average¡Ü90%£¬monthly averange of vapour pressure¡Ü1.8kpa. 
    4.Earthquake intensity: ¡Ümagnitude 8. 
    5.Applicable in the places without corrosive and flammable gas.
    Note: Customized products are available.




  • No.

    Item

    Unit

    Parameter

    Load switch

    Load switch + fuse

    1

    Rated current£¨Maximum voltage£©

    KV

    3.6 ¡¢7.2 ¡¢12

    2

    Rated frequency

    HZ

    50

    3

    Rated current

    A

    630

    100

    4

    Rated short-time withstand current

    KA

    20

    /

    5

    Rated peak withstand current

    KA

    50

    /

    6

    Rated short circuit duration (main circuit / ground loop)

    S

    3/2

    /

    7

    Rated short circuit closing current

    KA

    50

    80

    8

    Rated short-circuit breaking current

    KA

    /

    31.5

    9

    Rated transfer current

    A

    /

    1700

    10

    Rated power frequency withstand voltage

    Interphase

    KV

    42

    £¨1min£©

    Fracture room

    KV

    48

    11

     

    Interphase

    KV

    75

    Rated lightning impulse withstand voltage

    Fracture room

    KV

    85

    12

    Auxiliary and control loop to ground short-duration power frequency withstand voltage

    KV

    2000

    13

    Protection level

    V

    IP3X



  • HXGN15-12 Air-insulated Ring Main Unit.pdf

  • * Name£º 
    * Tel£º 
    * Email£º 
    * Content£º 
    ¡¡